Products name: XBD type fire fighting pumpsProduct introduction:1. LYSON XBD - ISG (ISW) type vertical fire pump single suction single stage and single suction multistage type two kinds, for the transport of water and physical and chemical properties not containing solid particles similar to the use of liquid water.2. Mainly use

Featured Products


Fire Fighting Pumps with Fire Hydrant Pump
Products name: XBD type fire fighting pumps

Product introduction:

1. LYSON XBD - ISG (ISW) type vertical fire pump single suction single stage and single suction multistage type two kinds, for the transport of water and physical and chemical properties not containing solid particles similar to the use of liquid water.

2. Mainly used for pressurized water supply in fire control system, can also be used in factories and mines, water supply and drainage.

3. Transport of liquid flow rate range of 5 ~ 80L / s,

4. The pressure range of 0.2 ~ 2.25MPa,

5. Supporting the power range of 1.5~200kW,

6. The scope of diameter 50 ~ 250mm.

Product features:

1 pump has the advantages of compact structure, small volume, beautiful appearance, its vertical structure decided to install a small area, center of gravity into the center of the foot pump, thus enhancing the operation stability and service life of the pump.

2 pump inlet and outlet are horizontal, which has simplified the connection of pipeline.

3 stage type according to the need, inlet and outlet can be installed to the same direction or 90., 180., 270. Several different directions to meet different connection conditions.

4 pump pressure can be added or deleted pump series and cutting impeller diameter to be met, without changing the installation area, this is other pumps do not have.
Around 5 pump rotor with smaller, stable running, small vibration, low noise, long service life.

Product use:

XBD ISG (ISW) fire pumps are mainly used for pressurized water supply pipeline fire control system. Can also be used for industrial and city water supply and drainage, pressurized water supply in high-rise constructions, distant distance water supply, heating boiler, cold and hot water circulation pressurization bathroom, air-conditioning refrigeration system water supply and equipment etc...
Fire Fighting Pumps with Fire Hydrant Pump
fault phenomenonfailure causeelimination methods
 1.No power supply or one or two phase power supply is needed 
Check all phases of power supply and restore power supply
 
 
 2.Poor contact of ac contactor and burning of coil 
Repair or replace contactors
 
 
can not start3.
The power switch is not closed, malfunction or damaged
 
 
Close the switch and replace it if the power indicator does not turn on
 4.
Thermal relay trip or damage
 
 
Check whether the motor is blocked, find out the reason and eliminate it.Manual reset is replaced if it cannot be started
 Water level is too low 
Put water in the sink
 
 
 The motor burned 
Repair or replace the motor
 
 
 1.Line is loose 
Check wiring and tighten connectors
 
 
 2.Frequency converter malfunctionCheck the fault content, check the cause according to the frequency converter manual, and restart after reset.Or disconnect the inverter power supply for a few seconds, the inverter fault reset before starting.
The manual is normal3The frequency converter is damagedRepair or replace
Automatic transmission failure4.Pressure switch damageRepair or replace
 5The pressure transmitter is damagedRepair or replace
 6.Switch failureRepair or replace
Pump non - suction pressure gauge pointer to beat violentlyInsufficient water supply for perfusion, air leakage at the connection between pipeline and instrumentCheck pipeline and bottom valve, refill water diversion. Tighten air leakage
 
The pump consumes too much power
 
 
 
Too much flow, impeller wear
 
 
Check whether the pump shaft is bent, replace the impeller, close the outlet valve to reduce the flow
Fire Fighting Pumps with Fire Hydrant Pump
Fire Fighting Pumps with Fire Hydrant Pump
Fire Fighting Pumps with Fire Hydrant Pump
Fire Fighting Pumps with Fire Hydrant Pump

About LYSON

♦ ESTABLISHED IN THE SIXTIES


♦ THROUGH THE ISO9001:2015 DOMESTIC,

INTERNATIONAL QUALITY SYSTEM CERTIFICATION


♦ SILVER MEDAL WAS AWARDED AT THE NATIONAL CONFERENCE ON THE

APPLICATION OF SPARK CUP TECHNOLOGY


♦ WIN THE NATIONAL AWARD FOR EXCELLENCE IN CIVILIZATION COMPETITION 


♦ GET THE LC OF THE CHINESE GOVERNMENT

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours