Firefighting frequency conversion constant pressure firefighting water supply equipment

Products Name: Automatic Constant Pressure Variable Flow Water Water Pump Water Supply EquipmentConditions of use: Suitable for conveying the temperature under 60 celsius water and similar to that of liquid water, pump system working pressure of up to 11 bar.The scope of performance parameter: This series a total of 6 species, 5

Featured Products



Fire Frequency Conversion Constant Pressure Fire Water Supply Equipment





Products Name: Automatic Constant Pressure Variable Flow Water Water Pump Water Supply Equipment

Conditions of use: Suitable for conveying the temperature under 60 celsius water and similar to that of liquid water, pump system working pressure of up to 11 bar.

The scope of performance parameter: This series a total of 6 species, 50kinds of specifications and its

performance parameters range:

1 flow Q= 18~108 m3/h

2. Lift H= 30 ~ 160 m

3. Speed n=1450/2900  r/mi8

4. Power P=1.1~ 274kW
fault phenomenonfailure causeelimination methods
The manual is normal
Automatic transmission failure
1.No power supply or one or two phase power supply is needed
Check all phases of power supply and restore power supply

 
Water level is too low
Put water in the sink

 
The motor burned
Repair or replace the motor

 
1.Line is loose
Check wiring and tighten connectors

 
2.Frequency converter malfunctionCheck the fault content, check the cause according to the frequency converter manual, and restart after reset.Or disconnect the inverter power supply for a few seconds, the inverter fault reset before starting.
3The frequency converter is damagedRepair or replace
4.Pressure switch damageRepair or replace
5The pressure transmitter is damagedRepair or replace
 6.Switch failureRepair or replace
Pump non - suction pressure gauge pointer to beat violentlyInsufficient water supply for perfusion, air leakage at the connection between pipeline and instrumentCheck pipeline and bottom valve, refill water diversion. Tighten air leakage

The pump consumes too much power

 

Too much flow, impeller wear

 
Check whether the pump shaft is bent, replace the impeller, close the outlet valve to reduce the flow



Fire Frequency Conversion Constant Pressure Fire Water Supply Equipment
Fire Frequency Conversion Constant Pressure Fire Water Supply Equipment